ProSoft Technology 5105-103M-PDPS User Manual

Page 67

Advertising
background image

5105-103M-PDPS ♦ ProLinx Gateway

Diagnostics and Troubleshooting

IEC 60870-5-103 Master to PROFIBUS Slave Gateway

User Manual

ProSoft Technology, Inc.

Page 67 of 144

November 24, 2010

Status Register [1]
SPC3 ASIC slave status information provided to the master.

Bits
0 to 3

Baud rate:
The baud rates SPC3 found

0000 = 12 MBaud
0001 = 6 MBaud
0010 = 3 MBaud
0011 = 1.5 MBaud
0100 = 500 kBaud
0101 = 187.5 kBaud
0110 = 93.75 kBaud
0111 = 45.45 kBaud
1000 = 19.2 kBaud
1001 = 9.6 kBaud
Rest = Not possible

Bits
4 to 7

SPC3-Release:
Release no. for SPC3

0000 = Release 0
Rest = Not possible

Diagnostic State
 0 = Normal Operation or not in data exchange with Status Register [0] Bit

0x20 set.

 1 = Not in data exchange state with the Status Register [0] bit 0x20 not set or

normal operation with the Status Register [0] bit 0x20 not set.

 3 = Not in a defined state or in module state 1, 2 or 3.
 4 = Normal operation with Status Register [0] bit 0x20 set

PROFIBUS Input Counter
Input counter is incremented each time the input data is updated.

PROFIBUS Output Counter
Output counter is incremented each time the output data is updated.