ProSoft Technology 5105-103M-PDPS User Manual

Page 108

Advertising
background image

Reference

5105-103M-PDPS ♦ ProLinx Gateway

User Manual

IEC 60870-5-103 Master to PROFIBUS Slave Gateway

Page 108 of 144

ProSoft Technology, Inc.

November 24, 2010

TYPE 9: Measurands II

Bytes

Description

Spec

1

Value of 9

1

I = 1 to 9 for number of values

1

COT

1

Common address of ASDU

1

Function Type

1

Information number

2

Current L

1

7.2.6.8

2

Current L

2

7.2.6.8

2

Current L

3

7.2.6.8

2

Voltage L

1-E

7.2.6.8

2

Voltage L

2-E

7.2.6.8

2

Voltage L

3-E

7.2.6.8

2

Active power P

7.2.6.8

2

Reactive power Q

7.2.6.8

2

Frequency f

7.2.6.8

Value of I determines number of parameters passed in the message with a range

of 1 to 9 but always starts with the L

1

value.

Definition and Presentation of ASDUs in Control Direction

TYPE 6: Time synchronization

Bytes

Description

Spec

1

Value of 6

1

0x81

1

COT

1

Common address of ASDU

1

Function Type = GLB (255)

1

Information number

7

7-Octet binary time

7.2.6.29

TYPE 7: Initiation of general interrogation

Bytes

Description

Spec

1

Value of 7

1

0x81

1

COT

1

Common address of ASDU

1

Function Type = GLB (255)

1

Information number

1

SCN (scan number 0 to 255)

7.2.6.21

Advertising
This manual is related to the following products: