5105-103M-PDPS ♦ ProLinx Gateway

Diagnostics and Troubleshooting

IEC 60870-5-103 Master to PROFIBUS Slave Gateway

User Manual

ProSoft Technology, Inc.

Page 65 of 144

November 24, 2010

The SPC3 is able to identify the baud rate automatically. The "baud search" state

is located after each RESET and also after the watchdog (WD) timer has run out

in the "Baud_Control_state." As a rule, SPC3 begins the search for the set rate

with the highest baud rate. If no SD1 telegram, SD2 telegram, or SD3 telegram

was received completely and without errors during the monitoring time, the

search continues with the next lowest baud rate.
After identifying the correct baud rate, SPC3 switches to the "Baud_Control"

state and monitors the baud rate. The monitoring time can be parameterized

(WD_Baud_Control_Val). The watchdog works with a clock of 100 Hz (10

milliseconds). The watchdog resets each telegram received with no errors to its

own station address. If the timer runs out, SPC3 again switches to the baud

search state.

Further explanation of Status Register [0]: Word 9 Bit states
Bit 0
Offline/Passive-idle
 0 = SPC3 exits offline and goes to passive-idle. The idle timer and Wd timer

go offline.

 1= SPC3 exits offline and goes to passive-idle. The idle timer and Wd timer

are started.

Bit 4, 5
 10 = Data Exchange State is Normal. The SPC3 has a correct configuration.
Bits 6, 7
 Watchdog Timer
 Automatic Baud Rate Identification
The SPC3 is able to identify the baud rate automatically. The "baud search" state

is located after each RESET and also after the watchdog (WD) timer has run out

in the "Baud_Control_state." As a rule, SPC3 begins the search for the set rate

with the highest baud rate. If no SD1 telegram, SD2 telegram, or SD3 telegram

was received completely and without errors during the monitoring time, the

search continues with the next lowest baud rate.
After identifying the correct baud rate, SPC3 switches to the "Baud_Control"

state and monitors the baud rate. The monitoring time can be parameterized

(WD_Baud_Control_Val). The watchdog works with a clock of 100 Hz (10

milliseconds). The watchdog resets each telegram received with no errors to its

own station address. If the timer runs out, SPC3 again switches to the baud

search state.