1.8

PDPS Protocol Configuration

The following illustration from ProSoft Configuration Builder shows the

PROFIBUS Slave configuration for a ProLinx PDPS module.

1.8.1 [PROFIBUS SLAVE]

The PROFIBUS Slave section contains the data that applies to the PROFIBUS

Slave parameters.

Slave Address
0 to 125
The parameter specifies the node address on the PROFIBUS network for the

slave emulated in the module. Each node on the network must have a unique

address.

Note: Although valid PROFIBUS Node addresses range from 0 to 125, Node 0 is not a valid node
number for a Slave module and that Nodes 0, 1, and 2 are usually reserved for PROFIBUS
Masters. Users are advised to use Node numbers 3-125

Swap Input Bytes
Yes or No
This parameter specifies if the data in the input data area of the module is to be

byte swapped. If the order of the bytes in the words stored in the database is not

correct, use this option. A value of Yes causes the module’s program to swap the

bytes in each word. A value of No indicates no byte swapping will occur.