5105-103M-PDPS ♦ ProLinx Gateway

Start Here

IEC 60870-5-103 Master to PROFIBUS Slave Gateway

User Manual

ProSoft Technology, Inc.

Page 35 of 144

November 24, 2010

Baud Rate
Baud Rate Value
This is the baud rate to be used on the port. Enter the baud rate as a value. For

example, to select 19K baud, enter 19200. Valid entries for this field include: 110,

150, 300, 600, 1200, 2400, 4800, 9600, 19200 (may also enter as 192 or 1920),

28800 (may also enter 288 or 2880), 38400 (may also enter as 384 or 3840),

57600 (may also enter as 576 or 5760), and 115200 (may also enter as 115,

1152, or 11520).

Parity
N, O, E, M, or S
This parameter sets the parity to be used on the port. The values correspond to

the following settings: N=None, O=Odd, E=Even, M=Mark and S=Space.

Note: The 103M specification supports only Even Parity.

RTS On
0 to 65535

milliseconds

This parameter sets the number of milliseconds to delay after Ready To Send

(RTS) is asserted before data will be transmitted.

RTS Off
0 to 65535 milliseconds
This parameter sets the number of milliseconds to delay after the last byte of

data is sent before the RTS modem signal will be set low.

Minimum Delay
1 to 60000 milliseconds
This parameter specifies the minimum number of milliseconds to delay before

sending the message (setting RTS high). This can be used when the serial

network requires time for units to turn off their transmitters.

Receive Timeout
1 to 65535 milliseconds
This value represents the number of milliseconds to wait on a port from the time

the first character is received until the last character in the longest message is

received. This parameter will be dependent on the baud rate. A value of 2000

should work with most applications.

Single char ACK F0, 1, or 3
Yes or No
This parameter specifies if the signal E5 character will be used for ACK

messages.