Diagnostics and Troubleshooting

5105-103M-PDPS ♦ ProLinx Gateway

User Manual

IEC 60870-5-103 Master to PROFIBUS Slave Gateway

Page 62 of 144

ProSoft Technology, Inc.

November 24, 2010

Cfg Len is the configuration length for the slave with S as the pointer.
RCfg len is that received from the master with S as the pointer.
Ident is the PROFIBUS identification number for the module.
FDL SAP last PTR is the end of all the PDPS data in the SPC3 chip. A value

greater than 0xFF indicates a memory overflow problem.
Comm Failure mode is that from the configuration file as is the swapping of

input and output data.

2.4.2 Definition of Module’s Extended Diagnostics Data

The Extended Diagnostic Data is reported during startup and initialization

sequence when the master requests diagnostic data from the module. The

Extended Diagnostics is "Device Related" type providing status data (the

extended diagnostic bit 3 in standard diagnostic byte 1 is set = 0). The data

length is normally 14 (0E) bytes displayed in the following format:

Byte(s)

Description (HEX)

0

Extended Diagnostics length (normally 14 bytes (0E))

1 to 6

ASCII data for Product Version

7 to 10

ASCII data for Product Name

11

Value of Status Register [0] (page 64)

12

Value of Status Register [1] (page 67)

13

Module State (page 63)

Bytes 7 through 10 Data - Specific Product Code Value
Each ProLinx application has its own, unique product code. You can determine

the product code from the Version screen in the Configuration/Debug menu.
The following table lists the product codes for some ProLinx modules that

support the PDPS protocol.

Example Product

Example Product Code

5105-ASCII-PDPS

ASPS

5105-DFCM-PDPS

DFPS

5105-DH485-PDPS

D4PS

5105-DNPM-PDPS

DMPS

5105-DNPS-PDPS

D3PS

5105-101S-PDPS

ISPS

5105-103M-PDPS

PSI3

5105-MCM-PDPS

PDSM