Diagnostics and Troubleshooting

5105-103M-PDPS ♦ ProLinx Gateway

User Manual

IEC 60870-5-103 Master to PROFIBUS Slave Gateway

Page 76 of 144

ProSoft Technology, Inc.

November 24, 2010

2.9

Data Analyzer

The data analyzer mode allows you to view all bytes of data transferred on each

port. Both the transmitted and received data bytes are displayed. Use of this

feature is limited without a thorough understanding of the protocol.

Note: The Port selection commands on the Data Analyzer menu differs very slightly in different
modules, but the functionality is basically the same. Use the illustration above as a general guide
only. Refer to the actual data analyzer menu on your module for the specific port commands to
use.
Important: When in analyzer mode, program execution will slow down. Only use this tool during a
troubleshooting session. Before disconnecting from the Config/Debug port, please press [S]

to stop

the data analyzer, and then press [M]

to return to the main menu. This action will allow the module

to resume its normal high speed operating mode.

2.9.1 Analyzing Data for the first application port

Press [1]

to display I/O data for the first application port in the Data Analyzer. The

following illustration shows an example of the Data Analyzer output.

2.9.2 Analyzing Data for the second application port

Press [2]

to display I/O data for the second application port in the Data Analyzer.

2.9.3 Displaying Timing Marks in the Data Analyzer

You can display timing marks for a variety of intervals in the data analyzer

screen. These timing marks can help you determine communication-timing

characteristics.

Key

Interval

[5]

1 milliseconds ticks

[6]

5 milliseconds ticks

[7]

10 milliseconds ticks

[8]

50 milliseconds ticks

[9]

100 milliseconds ticks

[0]

Turn off timing marks