Reference

IEC 60870-5-103 Master to PROFIBUS Slave Gateway

User Manual

ProSoft Technology, Inc.

Page 99 of 144

November 24, 2010

Error

Description

603

Illegal session

604

Session is reserved

605

Session is not available

701

No memory to transmit message

702

ASDU not supported

703

Duplicate request

704

Illegal sector

705

Control mode is illegal

801

Partial stop request

802

Stop request failed

902

Negative COT in response

903

Session is offline

904

Session is disabled

905

Select confirmation received, waiting to execute

906

Execute confirmation has not been received.

103M Protocol Support
This section describes the portions of IEC 60870-5-103 protocol that are

supported by the module.

Note: Shaded areas are not supported by the module.

List of Type Identification Codes

In Monitor Direction

Type

Description

1

time-tagged message

2

time-tagged message with relative time

3

measurands l

4

time-tagged measurands with relative time

5

identification

6

time synchronization

8

general interrogation termination

9

measurands ll

10

generic data

11

generic identification

23

list of recorded disturbances

26

ready for transmission of disturbance data

27

ready for transmission of channel

28

ready for transmission of tags

29

transmission of tags

30

transmission of disturbance values

31

end of transmission