3.1.3 Using ProSoft Configuration Builder

ProSoft Configuration Builder (PCB) provides a quick and easy way to manage

gateway configuration files customized to meet your application needs. PCB is

not only a powerful solution for new configuration files, but also allows you to

import information from previously installed (known working) configurations to

new projects.

3.1.4 PROFIBUS Slave Port Specifications

Type

Specifications

General Parameters
Internal Database

Up to 4000 registers (words) available.

GSD File

pgwa05a5.gsd
Downloadable from www.prosoft-technology.com

web site

PROFIBUS Slave

Communication parameters

Baud Rate: 9.6 kbps to 12 Mbps

Supported I/O length

122 words Input data
122 words Output data
200 words max

Supported PROFIBUS DP features

Freeze Mode
Sync Mode
Auto Baud Setting

Configurable Parameters

a) PROFIBUS Node Address: 0 to 125
b) Data byte swapping
c) Action on loss of PROFIBUS connection
d) Comm Fail Timeout Multiplier
e) Status Data location in Internal Database

Status Data

Error codes available on an individual command
basis. In addition, a slave status list is maintained

per active PROFIBUS Slave port.

Physical Connection

PROFIBUS Connector

Standard PROFIBUS DB-9F communication
connector. Cable connection matches PROFIBUS

pin out specification.

Important Note: The slave node address is set to 126 by default in the module configuration file.
The default node address must be changed to a valid address between 0 to 125 by the user for the
slave to function on the PROFIBUS network.