Example Response Block From GW

Start Byte

End Byte

Description

0

0

201 (Get Time)

1

1

200 (Set Time)

2

3

Year

4

5

Month

6

7

Day

8

9

Hour

10

11

Minutes

12

13

Seconds & milliseconds

14

197

Reserved for future use

198

198

Events in buffer (0 to 99)

199

199

201 (Get Time)

Event Data Block Format
Block 100 to 101 identification codes are used to pass events to the PLC when

the Pass Through Event parameter is enabled (Yes). The PROFIBUS Slave

sends events to the 103M master, then the 103M Master sends them over

PROFIBUS from the Slave to the PROFIBUS Master.

Start Byte

End Byte Data Field(s)

Description

0

0

Block ID

This field contains the value of 100 to 101 identifying

the block type to the module.

1

1

Last PLC Block ID Last block number for data received from PLC

2

3

Event Count

Number of events present in the block. This field can

have a value from 0 to 9.

4

23

Event #1

Event data from IED’s.

24

43

Event #2

Event data from IED’s.

44

63

Event #3

Event data from IED’s.

64

83

Event #4

Event data from IED’s.

84

103

Event #5

Event data from IED’s.

104

123

Event #6

Event data from IED’s.

124

143

Event #7

Event data from IED’s.

144

163

Event #8

Event data from IED’s.

164

183

Event #9

Event data from IED’s.

184

197

Reserved

Reserved for future use.

198

198

Buffer Count

Number of events present in the event buffer of the

103 master driver (0 to 99)

199

199

Block ID

Copy of byte 0 in the block.