Diagnostics and Troubleshooting

5105-103M-PDPS ♦ ProLinx Gateway

User Manual

IEC 60870-5-103 Master to PROFIBUS Slave Gateway

Page 64 of 144

ProSoft Technology, Inc.

November 24, 2010

Status Register [0]
SPC3 ASIC slave status information provided to the master.

Bit 0

Offline/Passive-Idle
Offline-/Passive-Idle state

0 = SPC3 is in offline
1 = SPC3 in passive idle

Bit 1

FDL_IND_ST (Fieldbus Data link Layer)
FDL indication is temporarily buffered.

0 = No FDL indication is temporarily buffered.
1 = FDL indication is temporarily buffered.

Bit 2

Diag_Flag
Status diagnostics buffer

0 = The DP master fetches the diagnostics buffer.
1 = The DP master has not yet fetched the diagnostics buffer.

Bit 3

RAM Access Violation
Memory access > 1.5kByte

0 = No address violation
1 = For addresses > 1536 bytes, 1024 is subtracted from the current address, and

there is access to this new address.

Bits 4,5 DP-State

DP-State Machine state

00 = 'Wait_Prm' state
01 = 'Wait_Cfg' state
10 = 'DATA_EX' state
11 = Not possible

Bits 6,7 WD-State

Watchdog-State-Machine state

00 = 'Baud_Search' state
01 = 'Baud_Control' state
10 = 'DP_Control' state
11 = Not possible

Bit 0
Offline/Passive-idle
 0 = SPC3 exits offline and goes to passive-idle. The idle timer and Wd timer

go offline.

 1= SPC3 exits offline and goes to passive-idle. The idle timer and Wd timer

are started.

Bit 4, 5
 10 = Data Exchange State is Normal. The SPC3 has a correct configuration.
Bits 6, 7
 Watchdog Timer
 Automatic Baud Rate Identification