Pass-Through
The pass-through features allows you to page through the ProLinx data 4000

registers over the Profibus network, using mailbox commands. You can also use

mailbox commands to set and get time, and pass events. The following topics

describe the mailbox commands.

IMPORTANT NOTE: For these blocks to function properly over the Profibus network, the slave
must be configured for 100 words of input and 100 words of output, and the Pass-Through Events
parameter must be enabled in the configuration file, as shown in the following example.

Pass-Through Events : Y # Pass event messages through Profibus Interface
# (Y/N (N=Default))

Mailbox Commands

Start

Stop

Direction

Description

100

101

PLC to GW

Event Data

150

151

PLC to GW

Database write transfer

160

161

GW to PLC

Database read transfer

200

200

Both

Set Time

201

201

Both

Get Time

PLC = PROFIBUS master interface in PLC
GW = ProLinx Gateway

NOTES:
The block number for each device must be changed to trigger an operation.
The I/O data area is owned exclusively by only the PLC or GW.
A timeout must be implemented in the PLC in case the GW is not present.