5105-103M-PDPS ♦ ProLinx Gateway

Reference

IEC 60870-5-103 Master to PROFIBUS Slave Gateway

User Manual

ProSoft Technology, Inc.

Page 109 of 144

November 24, 2010

TYPE 20: General command

Bytes

Description

Spec

1

Value of 20

1

0x81

1

COT

1

Common address of ASDU

1

Function Type

1

Information number

1

DCO (1=Off, 2=On)

7.2.6.4

1

RII

7.2.6.19

RII is not to be processed within the protection equipment, but to be used as a

SIN of the return message.

3.2.2 PDPS Protocol Implementation

Module Internal Database
The internal database is central to the functionality of the module. This database

is shared between all the ports on the module and is used as a conduit to pass

information from one device on one network to one or more devices on another

network. This permits data from devices on one communication port/network to

be viewed and controlled by devices on another port/network. In addition to data

from the slave port, status and error information generated by the module can

also be mapped into the internal database.