Data Type
Data type file represents the ASDU type as follows:

Type

Description

6

Clock synchronization

7

General interrogation

20

General Command

Function Code

Code

Definition

128

Distance protection

160

Overcurrent protection

176

Transformer differential protection

192

Line Differential protection

255

Global function type

133

Meter Data for SIEMENS Devices

1

Reset Process

2

Class 2 Polls

x

User-defined

Note: The last item in the Function Code dropdown list is user-defined. If you select U

SER

D

EFINED

from the dropdown list, a text box will appear below the list. You may enter any function code in
this text box that will be accepted by the destination slave.

Point Index
Point Index specifies the address in the remote slave device of the point to

interact with.

Index Value

Description

1

Bit address with each point occupying 2 bits

2

Bit address with each point occupying 2 bits

3

Word address with each point occupying 4 words

4

Double-word address for the single float value

5

Byte address with each point occupying 12 bytes

9

Word address with each point occupying 9 words

Override Flag
0 or 1
Override Flag field is used for general commands to determine the value to be

written. If the override flag is clear (0), the value in the database will be utilized. If

the override flag is set (1), the value specified in the override value field will be

used.