ProSoft Technology 5105-103M-PDPS User Manual

Page 44

Advertising
background image

Start Here

5105-103M-PDPS ♦ ProLinx Gateway

User Manual

IEC 60870-5-103 Master to PROFIBUS Slave Gateway

Page 44 of 144

ProSoft Technology, Inc.

November 24, 2010

Parameter Data Structure
SPC3 evaluates the first seven data bytes (without user prm data), or the first

eight data bytes (with user prm data). The first seven bytes are specified

according to the standard. The eighth byte is used for SPC3-specific

communications. The additional bytes are available to the application.

Byte

Bit Position

Designation

7

6

5

4

3

2

1

0

0

Lock
Reg

Unio
Req

Sync
Req

Free
Req

WD on

Res

Res

Res

Station status

1

WD_Fact_1

2

WD_Fact_2

3

MinTSDR

4

Ident_Number_High

5

Ident_Number_Low

6

Group_Ident

7

Spec_User_Prm_Byte

8 to 243

User_Prm_Data

Byte 7

Spec_User_Prm_Byte

Bit

Name

Significance

Default State

0

Dis_Startbit

The start bit monitoring in the receiver
is switched off with this bit

Dis_Startbit = 1,
That is, start bit monitoring is disabled.

1

Dis_Stopbit

Stop bit monitoring in the receiver is
switched off with this bit

Dis_Stopbit = 0
That is, stop bit monitoring is enabled

2

WD_Base

This bit specifies the time base used to
clock the watchdog.
WD_Base = 0: time base 10 ms
WD_Base = 1: time base 1 ms

WD_Base = 0
That is, the time base is 10 ms.

3 to 4

Res

To be parameterized with 0

0

5

Publisher_Enable

DXB-publisher-functionality of the
SPC3 is activated with this bit

Publisher_Enable = 0, DXB-request-
telegrams are ignored;
Publisher_Enable = 1, DXB-request-
telegram are processed

6 to 7

Res

To be parameterized with 0

0

Advertising