5105-103M-PDPS ♦ ProLinx Gateway

User Manual

IEC 60870-5-103 Master to PROFIBUS Slave Gateway

Page 42 of 144

ProSoft Technology, Inc.

November 24, 2010

Swap Output Bytes
Yes or No
This parameter specifies if the data in the output data area of the module is to be

byte swapped. If the order of the bytes in the words stored in the database is not

correct, use this option. A value of Yes causes the module’s program to swap the

bytes in each word. A value of No indicates no byte swapping will occur.

Comm Failure Mode
No xfer on fail
Xfer on comm fail
This parameter sets the data transfer mode of the module's PROFIBUS output

image to the internal database when a communication failure on the PROFIBUS

interface is detected. If the parameter is set to "No xfer on fail", the output image

will continue to be transferred. If the parameter is set to "xfer on comm fail", the

output image will not be transferred and the last values will be retained.

Comm Timeout Multiplier
1 to 10
This parameter sets the communication timeout value for the module. The value

entered is multiplied by 125 milliseconds to determine the actual timeout value.

For example, a value of 1 specifies a communication timeout of 125 milliseconds.

Use Database Paging
Yes or No
This Parameter Enables or disables user access to the PDPS’s Database area

outside the section reserved for the PROFIBUS Protocol in the range of Word

400 to Word 3999.