Initialization
According to the IEC 60870-5-103 protocol, the Master should send a Reset FCB

(or Reset CU) request to all slaves on the network. The ProLinx 103M module

will only send the initialization requests to the Data Link Addresses that are

configured as sessions. Once the slave responds to the FCB request with an

ACK response, the master starts polling the slave. The master will continuously

send the Reset FCB request until it receives the ACK response.
The user may also configure the module to send time synchronization and

general interrogation requests once the slave has responded to the reset FGD

request. Refer to the configuration file for the initialization parameters.
If the slave is not responding to the initialization request, the user should verify

the following items in order to troubleshoot the configuration:
Verify that the slave address (Data Link Address) is configured as a session

(slave) in the module. For example, if the module has two sessions correctly

configured (Data Link Addresses 1 and 2), and the slave is configured with a
Data Link address of 3, the slave will not respond to the initialization request.
 Verify that the communication port parameter matches the network

parameters.

 Check cables
 Verify that the communication mode jumpers (RS-232 or RS-485) are set

correctly.

Data Transfer in Monitor Direction
The master driver cyclically polls data from the slaves. The data is classified into

two classes; Class 1 and Class 2. Events belong to Class 1 and analog data to

Class 2. The user may configure the module to set how frequently the master will

poll with both classes.
The slave will respond to a Class 2 poll with specific data points. The user can

configure these points in the ProLinx module in order to periodically update the

database with the point values. The other protocol can access these points using

the same database.

Data Transfer in Control Direction
The ProLinx 103M module can be configured to issue commands to the

configured slaves (sessions). The General Command can be used to transfer

data from the module to each slave. The user may associate a control data point

with a register in the internal database using the configuration file. The module

may also send a time synchronization request to the device.
The module supports up to 500 commands. Each command is associated with a

configured session and server. It is essential that the slave is correctly configured

in order to have successful command communication.