ProSoft Technology 5105-103M-PDPS User Manual

Page 28

Advertising
background image

Start Here

5105-103M-PDPS ♦ ProLinx Gateway

User Manual

IEC 60870-5-103 Master to PROFIBUS Slave Gateway

Page 28 of 144

ProSoft Technology, Inc.

November 24, 2010

Step 6: Command Configuration (Control Direction)
You can also configure the master to send commands to slaves. The IEC 60870-

5-103 protocol specification refers to this data flow as Control Direction. The

commands include general commands, interrogation requests, and time

synchronization requests. In order to configure a command, refer to the [IEC-103
Master Commands]

section:

To send a General Command, you can associate the source data with a register

in the module database to be sent to the remote slave. The following example

will send 8 commands to the slave configured as Session 0/Sector 0. Use bit

addressing to send a General Command.

Refer to the device specification for the Point Index (Information Number) listing

available for control direction.
The module can also send a periodic General Interrogation command in order to

initialize and refresh the event-updated points in its database. The slave keeps a

list of all data subject to General Interrogation.

Advertising
This manual is related to the following products: