5105-103M-PDPS ♦ ProLinx Gateway

Diagnostics and Troubleshooting

IEC 60870-5-103 Master to PROFIBUS Slave Gateway

User Manual

ProSoft Technology, Inc.

Page 79 of 144

November 24, 2010

After you have selected the Port, Format, and Tick, we are now ready to start a

capture of this data. The easiest way to do so is to go up to the top of you

HyperTerminal window, and do a T

RANSFER

/

C

APTURE

T

EXT

as shown below:

After selecting the above option, the following window will appear:

Next name the file, and select a directory to store the file in. In this example, we

are creating a file ProSoft.txt and storing this file on our root C: drive. After you

have done this, press the

button.

Now you have everything that shows up on the HyperTerminal screen being

logged to a file called ProSoft.txt. This is the file that you will then be able to

email to ProSoft Technical Support to assist with issues on the communications

network.
To begin the display of the communications data, you will then want to press [B]

to tell the module to start printing the communications traffic out on the debug

port of the module. After you have pressed [B],

you should see something like

the following: