ProSoft Technology 5105-103M-PDPS User Manual

Page 114

Advertising
background image

Reference

5105-103M-PDPS ♦ ProLinx Gateway

User Manual

IEC 60870-5-103 Master to PROFIBUS Slave Gateway

Page 114 of 144

ProSoft Technology, Inc.

November 24, 2010

Mailbox From PLC to Gateway

Start Byte

End Byte

Description

0

0

Block number of data in block

1

1

Block number of data requested

2

198

Data for block

199

199

Block number of data in block

Mailbox From GW to PLC

Start Byte

End Byte

Description

0

0

Block number of data in block

1

1

Last block number received from PLC

2

197

Data for block

198

198

Events in buffer (0 to 99)

199

199

Block number of data in block

Example Raw Database Exchange from PLC

Start Byte

End Byte

Description

0

0

150 (Raw data write)

1

1

160 (Raw data read)

2

3

Start register in database for write

4

5

Number of registers to write (1 to 94)

6

7

Start register in database for read

8

9

Number of registers to read (1 to 96)

10

197

Words to write to the database

198

198

Reserved for future use

199

199

150 (Raw data write)

Example Response Block From GW

Start Byte

End Byte

Description

0

0

160 (Raw data read)

1

1

150 (Raw data write)

2

3

Start register in database for read

4

5

Number of registers to read (1 to 96)

6

197

Words read from the database

198

198

Events in buffer (0 to 99)

199

199

160 (Raw data read)

Advertising
This manual is related to the following products: