5105-103M-PDPS ♦ ProLinx Gateway

Start Here

IEC 60870-5-103 Master to PROFIBUS Slave Gateway

User Manual

ProSoft Technology, Inc.

Page 39 of 144

November 24, 2010

Common ASDU Address
0 to 255
This parameter sets the common ASDU address to association with this sector of

the specified session. This parameter is usually set the same as the Data Link
Address
when only one sector is used.

Online Time Sync
Yes or No
This parameter specifies if the sector in the controlled device will be sent a time

synchronization command when the unit is first recognized as being online. This

should only be used for devices that do not send an EOI message after

initializing.

Online General Int
Yes or No
This parameter specifies if the sector in the controlled device will be sent a

general interrogation command when the unit is first recognized as being online.

This should only be used for devices that do not send an EOI message after

initializing.

EOI Time Sync
Yes or No
This parameter specifies if the sector in the controlled device will be sent a time

synchronization command after this module received an EOI message from the

controlled unit.

EOI General Int
Yes or No
This parameter specifies if the sector in the controlled device will be sent a

general interrogation command after this module received an EOI message from

the controlled unit.

ASDU Type
This field contains the ASDU type code for the data contained in the message.
 1 = Time-tagged message (bit addressed with 2 bits/point)
 2 = Time-tagged message with relative time (bit addressed with 2 bits/point)
 3 = Measurands I (4 word values using word address using double-word

address)

 4 = Time-tagged measurands with relative time (1 float value)
 5 = Identification (12 characters using a byte address)
 9 = Measurands II (9 word values using word address)
 205 = Siemens meter data