ProSoft Technology 5105-103M-PDPS User Manual

Page 90

Advertising
background image

Reference

5105-103M-PDPS ♦ ProLinx Gateway

User Manual

IEC 60870-5-103 Master to PROFIBUS Slave Gateway

Page 90 of 144

ProSoft Technology, Inc.

November 24, 2010

3.1.5 Serial Port Specifications

Type

Specifications

Serial Ports
Serial Port Adapter Cables

One Mini DIN to DB-9M adapter cable included for

each configurable serial port

Config Port Connector/ Pinout

DB-9F connector / DTE pinout

Serial Port Isolation

2500V RMS port-to-port isolation per UL 1577.
3000V DC min. port to ground and port to logic

power isolation.

Serial Port Protection

RS-485/422 port interface lines TVS diode protected

at +/- 27V standoff voltage.
RS-232 port interface lines fault protected to +/- 36V

power on, +/- 40V power off.

Note: On all ProLinx gateways, data from the application port on the main board, serial Port 0, is
not buffered. Packets go directly to and from the serial chipset to the processor. This has the
potential to cause the serial communications to become erratic at baud rates above 38,400 baud.
ProLinx gateways with 4 serial ports have a separate serial interface board for serial Ports 1, 2,
and 3. These serial ports are buffered and can handle communications up to 115,200 baud.

Advertising
This manual is related to the following products: