Reference

5105-103M-PDPS ♦ ProLinx Gateway

User Manual

IEC 60870-5-103 Master to PROFIBUS Slave Gateway

Page 120 of 144

ProSoft Technology, Inc.

November 24, 2010

PROFIBUS Status Register: Word 10309
SPC3 ASIC slave status information provided to the master

Bit 0

Offline/Passive-Idle
Offline-/Passive-Idle state

0 = SPC3 is in offline
1 = SPC3 in passive idle

Bit 1

FDL_IND_ST (Fieldbus Data link Layer)
FDL indication is temporarily buffered.

0 = No FDL indication is temporarily buffered.
1 = FDL indication is temporarily buffered.

Bit 2

Diag_Flag
Status diagnostics buffer

0 = The DP master fetches the diagnostics buffer.
1 = The DP master has not yet fetched the diagnostics buffer.

Bit 3

RAM Access Violation
Memory access > 1.5kByte

0 = No address violation
1 = For addresses > 1536 bytes, 1024 is subtracted from the current address,

and there is access to this new address.

Bits 4,5 DP-State

DP-State Machine state

00 = 'Wait_Prm' state
01 = 'Wait_Cfg' state
10 = 'DATA_EX' state
11 = Not possible

Bits 6,7 WD-State

Watchdog-State-Machine state

00 = 'Baud_Search' state
01 = 'Baud_Control' state
10 = 'DP_Control' state
11 = Not possible

Bits
8 to 11

Baud rate:
The baud rates SPC3 found

0000 = 12 MBaud
0001 = 6 MBaud
0010 = 3 MBaud
0011 = 1.5 MBaud
0100 = 500 kBaud
0101 = 187.5 kBaud
0110 = 93.75 kBaud
0111 = 45.45 kBaud
1000 = 19.2 kBaud
1001 = 9.6 kBaud
Rest = Not possible

Bits
12 to 15

SPC3-Release:
Release no. for SPC3

0000 = Release 0
Rest = Not possible