3.4.12 Fault indications in monitor direction

INF

Semantics

<64>

Start /pick-up L

1

<65>

Start /pick-up L

2

<66>

Start /pick-up L

3

<67>

Start /pick-up N

<68>

General trip

<69>

Trip L

1

<70>

Trip L

2

<71>

Trip L

3

<72>

Trip I>> (back-up operation)

<73>

Fault location X in ohms

<74>

Fault forward/line

<75>

Fault reverse/busbar

<76>

Teleprotection signal transmitted

<77>

Teleprotection signal received

<78>

Zone 1

<79>

Zone 2

<80>

Zone 3

<81>

Zone 4

<82>

Zone 5

<83>

Zone 6

<84>

General start/pick-up

<85>

Breaker failure

<86>

Trip measuring system L

1

<87>

Trip measuring system L

2

<88>

Trip measuring system L

3

<89>

Trip measuring system E

<90>

Trip I>

<91>

Trip I>>

<92>

Trip IN>

<93>

Trip IN>>

3.4.13 Auto-reclosure indications in monitor direction

INF

Semantics

<128>

CB "on" by AR

<129>

CB "on" by long-time AR

<130>

AR blocked