ProSoft Technology 5105-103M-PDPS User Manual

Page 115

Advertising
background image

5105-103M-PDPS ♦ ProLinx Gateway

Reference

IEC 60870-5-103 Master to PROFIBUS Slave Gateway

User Manual

ProSoft Technology, Inc.

Page 115 of 144

November 24, 2010

Example Event Data Block From PLC

Start Byte

End Byte

Description

0

0

150 (Raw data write)

1

1

100 (Event data)

2

3

Start register in database for write

4

5

Number of registers to write (1 to 94)

6

7

Not Used

8

9

Not Used

10

197

Words to write to the database

198

198

Reserved

199

199

150 (Raw data write)

Example Response Block From GW

Start Byte

End Byte

Description

0

0

100 (Event data)

1

1

150 (Raw data write)

2

3

Event Count (0 to 9)

4

183

Event Data (0 to 9 event data structures)

184

197

Reserved for future use

198

198

Events in buffer (0 to 99)

199

199

100 (Event data)

Example Set Time Data Block From PLC

Start Byte

End Byte

Description

0

0

200 (Set Time)

1

1

201 (Get Time)

2

3

Year

4

5

Month

6

7

Day

8

9

Hour

10

11

Minutes

12

13

Seconds & milliseconds

14

198

Reserved for future use

199

199

200 (Set Time)