5105-103M-PDPS ♦ ProLinx Gateway

User Manual

IEC 60870-5-103 Master to PROFIBUS Slave Gateway

Page 32 of 144

ProSoft Technology, Inc.

November 24, 2010

Enable Code
0 = Disabled
1 = Enabled, will execute using Poll Interval parameter (page 32) (seconds)
2 = Conditional (executed when point in database changes)
This field defines whether the command is to be executed, and under what

conditions. To disable the command, set this parameter to 0 (Disabled). You can

still execute commands through the processor, using a Special Function block.
To enable the command, set this parameter to 1.
 Set the Poll Interval Time to 0 to execute the command during each scan of

the command list.

 Set the Poll Interval Time to a value in seconds, to execute the command at

the specified interval (page 32).

To execute the command only if the internal data associated with the command

changes, set this parameter to 2. This value is valid only for write commands.

Database Index
Database Index is the location in the module's database to use as the source for

the data in the command. Refer to Data Type for specific information on

addressing (page 33).
The data type field determines the meaning of the database index as follows:

Type

Description

DB Index type

6

Clock synchronization

NA

7

General interrogation

NA

20

General Command

Bit address

Poll Interval
This parameter specifies the minimum frequency at which the module should

execute the command when the Enable Code is set to one 1. The value is

entered in units of seconds. For example, to execute a command every 10

seconds, enter a value of 10 in the field. A value of 0

for the parameter implies

that the command should be executed every scan of the list, as quickly as

possible.

Session Index
0 to 31
Session Index represents the session index in the module to associate with the

command. This index is set when the session is read in from this file. The range

of values for this field is 0 to 31.

Sector Index
0 to 4
Sector Index represents the sector index for the specific session. There are a

maximum of five (5) sectors per session.