14 measurands in monitor direction, 15 generic functions in monitor direction, 18 general commands in control direction – ProSoft Technology 5105-103M-PDPS User Manual

Page 129

Advertising
background image

5105-103M-PDPS ♦ ProLinx Gateway

Reference

IEC 60870-5-103 Master to PROFIBUS Slave Gateway

User Manual

ProSoft Technology, Inc.

Page 129 of 144

November 24, 2010

3.4.14 Measurands in monitor direction

INF

Semantics

<144>

Measurand I

<145>

Measurands I, V

<146>

Measurands I, V, P, Q

<147>

Measurands I

N

, V

EN

<148>

Measurands I

L1,2,3

, V

L1,2,3

, P, Q, f

3.4.15 Generic functions in monitor direction

INF

Semantics



<240>

Read headings of all defined groups



<241>

Read values or attributes of all entries of one group



<243>

Read directory of a single entry



<244>

Read value or attribute of a single entry



<245>

End of general interrogation of generic data



<249>

Write entry with confirmation



<250>

Write entry with execution



<251>

Write entry aborted

3.4.16 Selection of standard information numbers in control direction

3.4.17 System functions in control direction

INF

Semantics

<0>

Initiation of general interrogation

<0>

Time synchronization

3.4.18 General commands in control direction

INF

Semantics

<16>

Auto-recloser on/off

<17>

Teleprotection on/off

<18>

Protection on/off

<19>

LED reset

<23>

Activate characteristic 1

<24>

Activate characteristic 2

<25>

Activate characteristic 3

<26>

Activate characteristic 4