Response Timeout
0 to 4,294,967,295 milliseconds
This parameter sets the maximum number of milliseconds to wait for a

confirmation from the controlled station to a request from this module.

ACTTERM with setpoint
Yes or No
This parameter determines if an ACTTERM will be sent. If the parameter is set to

Yes, then setpoint commands will issue an ACTTERM when the command is

complete. If the parameter is set to No, ACTCON is the last response to a
setpoint command.

1.7.5 [IEC-103 Master Session x Sector y]

This section defines Sector z, which belongs to Session y. The Sector Count

parameter (page 36) in the [IEC-870-5-103 Master Session y] section specifies

the number of sectors for the session.
Each sector has a corresponding [IEC-103 Master Session y Sector z] section,

where y represents the session index and z represents the sector index.
The sectors are referenced by a zero-based index value. For example, if Session

0 is configured for four sectors, the configuration file should contain sections for

Sectors 0 to 3 (that is, [IEC-103 Master Session 0 Sector 0] to [IEC-103 Master
Session 0 Sector 3]
).