ProSoft Technology 5105-103M-PDPS User Manual

Page 26

Advertising
background image

Start Here

5105-103M-PDPS ♦ ProLinx Gateway

User Manual

IEC 60870-5-103 Master to PROFIBUS Slave Gateway

Page 26 of 144

ProSoft Technology, Inc.

November 24, 2010

For each point, configure the following values.

ASDU Type: ASDU type for the point
Function Type: Function type for the point
Point Index: Information number for the point
Database Index: The module database location where the value will be copied.
The type of addressing will depend on the ASDU type:

ASDU Type

DB Addressing

1

Bit address with each point occupying 2 bits

2

Bit address with each point occupying 2 bits

3

Word address with each point occupying 4 words

4

Double-word address for the single float value

5

Byte address with each point occupying 12 bytes

9

Word address with each point occupying 9 words

For example, to configure the following points,
 Time-tagged message point with information number 17 (teleprotection

active) and distance protection function (128). The value will be copied to bits

0 and 1 in word 1 (second word) in the module database.

 Measurands I point with information number 144 (measurands I) and

overcurrent protection function (160). The value will be copied to word 50 in

the module Database.