Step 5: Monitor Point Configuration (Monitor Direction)
When a slave receives a Class 1 or Class 2 request from the master, it responds

with a message containing data. Each piece of equipment is normally configured

to respond with specific points when it is being polled with a Class 2 request.

During a Class 2 response, the slave may set a control bit (ACD) to inform the

master that there are new events to be transmitted. Then, the master will send a

Class 1 poll to read the events from the slave.
The IEC 60870-5-103 protocol states that the data is transferred between the

master and slave using an ASDU (Application Service Data Unit) format. Each

format is given by:

Type Identification

Variable Structure Qualifier
Cause Of Transmission
Common Address of ASDU
Function Type
Information Number
Data…
Data…

Refer to the protection equipment specification for the following information about

each point:
 Type: Type of the message
 Function Type: Type of protection function
 Information Number: Point Identification
This information identifies each point in the configuration. You must configure the

points that will be updated in the module database when a Class 2 or Class 1

response containing data is sent from the slave. Refer to [IEC-103

M

ASTER

S

ESSION X

S

ECTOR

0] to configure each point.