Grain temperature sensors (rtds), Installing conduit for rtds – Grain Systems PNEG-707GSI User Manual

Page 107

Advertising
background image

8. Sensors

PNEG-707 12', 18', 24' and 30' GSI Commercial Tower Dryer

107

Grain Temperature Sensors (RTDs)

Install RTDs on outside of dryer, within safe reach of ladder.

There is one (1) RTD on a 10' length of 1/2" conduit.

Position RTDs according to

Figure 8A on Page 97

. Drill hole in dryer wall for sensing bolt on each RTD.

Add one (1) 3/8" washer to bolt/washer already on each RTD. Insert sensing bolt in hole. Secure conduit
near RTD with 1/2" conduit hanger. Use existing bolts on seam.

NOTE: Do not place nut on inside of outside screen.

Placement of RTDs

Either RTD can be installed in top position.

R.H. Pair of RTDs

Install to right of outside ladder, and within reach of outside ladder.

Place R.H.-bottom RTD just above heat section floor.

R.H.-top RTD is on same conduit, 10' above bottom R.H. sensor.

L.H. Pair of RTDs

Install in next grain column over from R.H. pair of RTD, at the same level as R.H. pair, and within reach
of outside ladder.

Installing Conduit for RTDS

Run conduit parallel or perpendicular to other conduits and dryer features.

Vertical conduits should be plumb, neat, and orderly.

Figure 8V Grain sensor

is embedded in stainless steel bolt.

NOTE: Either RTD on conduit can be installed in top position.

A

A. RTD - Grain temperature sensor
B. Sensing bolt

B