NORD Drivesystems BU0260 User Manual

Page 21

Advertising
background image

2 Assembly and installation

BU 0260 GB

Subject to technical amendments

21

2.2.2

Control connections

The CANopen modules must be provided with a 24V DC (±20%, 100mA) control voltage. Wire end sleeves
must be used for flexible cables.

Designation

Data

Rigid cable cross-section

0.14 … 2.5mm²

Flexible cable cross-section

0.14 … 1.5mm²

AWG standard

AWG 26-14

Tightening torque (for screw terminals)

0.5…0.6Nm


Within the terminal box (unshielded cable section) the data cables (e.g. CANopen, system bus) must be
installed as short as possible and of equal length. Associated data cables (e.g.: Sys+ and Sys-) must be
twisted.

NOTE

Due to the separated potential levels of the system bus and the field bus (CANopen), both
bus systems must have a separate supply (24V).


NOTE

In the customer unit, the CAN open is already installed with voltage isolation from the other
signal connections.

In case of EMC problems, voltage separation of the field bus supply, the digital inputs and
system bus interface and for the external technology unit also for the two additional digital
outputs should be provided.



NOTE

The cable shielding must be connected to the functional earthing

1

(usually the

electrically conducting mounting plate) in order to prevent EMC interference in the
device.

In order to achieve this, for CANopen connections it is mandatory that the metallic metric
EMC screws are used for the connection of the CANopen shielding lead to the frequency
inverter or the housing of the technology unit. This ensures a wide area connection of the
functional earthing

.



1

In systems, electrical equipment is usually connected to a functional earth. This serves as a means to dissipate leakage

and interference currents in order to ensure EMC characteristics and must therefore be implemented according to high
frequency technology aspects.