5 Parameterisation

BU 0260 GB

Subject to technical amendments

67

5.2 Parameterisation of the bus module (SK CU4-… or SK TU4-…)

The following parameters affect the bus modules.
With access via CANopen, 0x2000 must be added to the parameter. Counting of the sub-indices begins with 1.

5.2.1

BUS module standard parameters (P150)

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P150 Set

relays

0 ... 4

{ 0 }

0 = Via bus
1 = Outputs OFF
2 = Output 1 to (DO1)
3 = Output 2 to (DO2)
4 = Outputs 1 and 2 ON

P151

Timeout for external bus

0 ... 32767 ms

{ 0 }

Monitoring function of the active bus technology unit. Following receipt of a valid telegram, the
next one must arrive within the set period. Otherwise the inverter reports an error and switches
off with the error message E010 / E10.2 >Bus Time Out< >Bus Time Out<.

0 = OFF: Monitoring is switched off.

Behaviour is identical to parameter (P513) telegram timeout for SK 200E.

P152 Factory

setting

0 ... 1

{ 0 }

By selecting the appropriate value and confirming it with the ENTER key, the selected
parameter range is entered in the factory setting. Once the setting has been made, the value of
the parameter returns automatically to 0.

0 = No change:Does not change the parameterisation.
1 = Load factory settings: The complete parameterisation of the FI reverts to the factory

setting. All originally parameterised data are lost.