NORD Drivesystems BU0260 User Manual

Page 80

Advertising
background image

Supplementary Manual CANopen for NORDAC SK 20E

80

Subject to technical amendments

BU 0260 GB

6.2.2

Table of possible error messages in the bus module

The following error messages concern bus-related messages, which are indicated on the CANopen module
(SK CU4-CAO or SK TU4-CAO(-…)).

Error number

Fault

Text in the ParameterBox

Cause

Remedy

Group

Details in
P170

E1000

1000 EEPROM

error

Module faulty

1010

System bus 24V missing

Check connections and supply cables

Ensure 24V voltage supply

1020

System bus timeout

Check time set in parameter (P151).

Telegram transfer is faulty.

Check external connection.

Check bus protocol program process.

Check bus master.

1030

System bus OFF

Check connections and supply cables

Ensure 24V voltage supply

Check bus master.

5110

CANopen bus OFF

Subscriber is disconnected from bus

5111 CANopen

warning

Bus error

No other subscriber present on the system bus

Wiring not correct (cable length, spur cables)

No valid ID (DIP switch)

5112 CANopen

overrun

Message box (message buffer) for the module was
overwritten by a new telegram before processing

Increase master inhibit time

Reduce baud rate

5113

Invalid CANopen address

Avoid double assignment of addresses

Comply with address range 1 ... 63

5120 CANopen

timeout

Telegram transfer is faulty.

Check external connection.

Check bus protocol program process.

Check bus master.