NORD Drivesystems BU0260 User Manual

Page 64

Advertising
background image

Supplementary Manual CANopen for NORDAC SK 20E

64

Subject to technical amendments

BU 0260 GB

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P552

[-01]

[-02]

System bus master cycle time

S

0 / 0.1 … 100.0 ms

{ 0 }

In this parameter, the cycle time for the system bus master mode and the CAN open encoder is
set (see P503/514/515):

… [01] = Cycle time for system bus master functions

… [02] = Cycle time for system absolute value encoder

With the setting 0 = "Auto" the default value (see table) is used.

According to the baud rate set, there are different minimum values for the actual cycle time:

Baud rate

Minimum value t

Z

Default system bus master

Default system bus

10kBaud 10ms

50ms

20ms

20kBaud 10ms

25ms

20ms

50kBaud 5ms

10ms

10ms

100kBaud 2ms

5ms

5ms

125kBaud 2ms

5ms

5ms

250kBaud 1ms

5ms

2ms

500kBaud 1ms

5ms

2ms

1000kBaud 1ms

5ms

2ms

P560

Save in EEPROM

S

0 ... 1

{ 1 }

0 = Changes to the parameter settings are no longer saved on the EEPROM. Previously

saved settings remain stored, even if the FI is disconnected from the mains; however
new changes are not saved after a mains failure.

1 = All parameter changes are automatically written to the EEPROM and remain stored there

even if the FI is disconnected from the mains supply.

NOTE:

If BUS communication is used to implement parameter changes, it must be
ensured that the maximum number of write cycles (100,000 x) in the EEPROM is
not exceeded.

Advertising