Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P543

[-01]

...

[-03]

Actual bus value 1 3

S

P

0 ... 22

{ [-01] = 01 }

{ [-02] = 04 }

{ [-03] = 09 }

The return value can be selected for bus actuation in this parameter.

NOTE:

For further details, please refer to the description for (P418).

… [-01] = Actual bus value 1

… [-02] = Actual bus value 2

… [-03] = Actual bus value 3

Possible values which can be set:

0 = Off
1 = Actual frequency
2 = Actual speed
3 = Current
4 = Torque current (100% = P112)
5 = State of digital inputs and outputs

2

6 = ... 7 Reserved
8 = Setpoint frequency
9 = Error number

10 = ... 11 Reserved
12 = Bus Out bits 0...7
13 = ... 16 Reserved
17 = Value analog input 1 (P400)
18 = Value analog input 2 (P405)
19 = Setpoint frequency master value (P503)
20 = Setpoint frequency after master value ramp
21 = Actual frequency without master value slip
22 = Speed from encoder

P546

[-01]

...

[-03]

Function Bus setpoint 1 ... 3

S

P

0 ... 24

{ [-01] = 01 }

{ [-02] = 00 }

{ [-03] = 00 }

In this parameter, a function is allocated to the output setpoint during bus actuation.

NOTE:

For further details, please refer to the description for (P400).

… [-01] = Actual bus value 1

… [-02] = Actual bus value 2

… [-03] = Actual bus value 3

Possible values which can be set:

0 = Off
1 = Setpoint frequency (16 bit)
2 = Frequency addition
3 = Frequency subtraction
4 = Minimum frequency
5 = Maximum frequency
6 = PI process controller actual value
7 = PI process controller setpoint
8 = Actual frequency PID
9 = Actual PID frequency limited

10 = Actual PID frequency monitored

11 = Limiting torque current
12 = Torque current switch-off limit
13 = Limiting current
14 = Current switch-off limit
15 = Ramp time
16 = Lead torque (P214) multiplication
17 = Servo mode torque
18 = Curve travel calculator
19 = Digital In bits 0...7
20 = ...24 reserved for Posicon

2

The assignment of the digital inputs for P543 = 5

Bit 0 = DigIn 1

Bit 1 = DigIn 2

Bit 2 = DigIn 3

Bit 3 = DigIn 4

Bit 4 = Reserved

Bit 5 = Reserved

Bit 6 = Reserved

Bit 7 = Reserved

Bit 8 = Reserved

Bit 9 = Reserved

Bit 10 = Reserved

Bit 11 = Reserved

Bit 12 = Out 1

Bit 13 = Out 2

Bit 14 = Reserved

Bit 15 = Reserved