2 Assembly and installation

BU 0260 GB

Subject to technical amendments

25

Control connection details

Terminal/
Designation

Function

Data

Description / wiring suggestion

Parameter

1 24V BUS
(CAO)

2

External 24V bus
supply
(field bus)

24VDC -/+20%
≈ 50 mA
reverse polarity protected

Max. permissible current
load: 3A

Supply voltage for the CANopen
controller / field bus

-

3 CANopen+

(incoming)

4

(outgoing)

Bus +

CAN H

RS485 transfer

The use of twisted, shielded two-
conductor cable is highly
recommended

-

5 CANopen-

(incoming)

6

(outgoing)

Bus -

CAN L

-

7 GND

BUS


8

Data ground bus

-

9 SHLD

Bus shield

-

10 PE

PE bus

-

Potential isolation

1124V

12

13

External 24V supply
(system bus)

24VDC -/+20%
≈ 50 mA
reverse polarity protected

Max. permissible current
load: 3A

Version to terminal 1 electrically
insulated.
CANopen bus supply (essential)

-

14 Sys+

System bus

data cable +

System bus
interface

-

15 GND

Reference potential
for digital signals

External supply voltage for system
bus and digital inputs (DIN1 to
DIN4)

-

16 Sys-

System bus

data cable -

System bus
interface

-

17 GND

18

Reference potential
for digital signals

External supply voltage for system
bus and digital inputs (DIN1 to
DIN4)

-

19 DIN1

Digital input 1
[I/O CANopen DIN1]

Low 0V ... 5V
High 15V ... 30V
R

i

= 8.1k

Input capacitance 10nF
Scan rate 1 ms

Each digital input has a reaction
time of 1ms.
Inputs as per
EN 61131-2

Type 1

P174

20 DIN3

Digital input 3
[I/O CANopen DIN3]

P174

21 GND

22

Reference potential
for digital signals

External supply voltage for system
bus and digital inputs (DIN1 to
DIN4)

-