5 parameterisation, 1 parameterising the sk 200e frequency inverter – NORD Drivesystems BU0260 User Manual

Page 58

Advertising
background image

Supplementary Manual CANopen for NORDAC SK 20E

58

Subject to technical amendments

BU 0260 GB

5 Parameterisation

In order to enable communication via CANopen, the frequency inverter and the CANopen Technology Unit
must be parameterised accordingly.
With the CANopen protocol, the inverter parameters are mapped in the range above 2000

hex

i.e. for

parameterisation via the bus, 2000

hex

must be added to the parameter numbers (e.g. (P508): 508

dez

= 1FD

hex

→ 2000

hex

+1FD

hex

=21FD

hex

).


5.1 Parameterising the SK 200E frequency inverter

The following list of parameters for the frequency inverter series SK 200E are directly relevant for the operation
of the frequency inverter via CANopen. A complete list of parameters for the frequency inverter LEDs (SK
200E) can be found in the relevant manual (BU0200).

5.1.1

Basic parameters (P100)

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P120

[-01]

...

[-04]

Option monitoring

S

0 ... 2

{ 1 }

Array levels:

Setting value for each array:

… [-01] = Extension 1 (BUS-TB)

… [-02] = Extension 2 (IO-TB)

… [-03] = Extension 3 (reserved)

… [-04] = Extension 4 (reserved)

0 = Monitoring OFF
1 = Auto
, communication is only monitored if an

existing communication is interrupted. If a
module which was previously present is not
found when the network is switched on, this
does not result in an error.
Monitoring only becomes active when the
extension begins communication with the FI.

2 = Monitoring active immediately; the FI starts

monitoring the corresponding module
immediately after it is switched on. If the
module is not detected on switch-on, the FI
remains in the status "not ready for switch-on"
for 5 seconds and then triggers an error
message.

Advertising