Supplementary Manual CANopen for NORDAC SK 20E

94

Subject to technical amendments

BU 0260 GB

Mapping

Byte

1

2

3

4

Rx-PDO1

Obj 0x3000 (Sub 1) (control word)

0bj. 0x3002 Sub1 (Setpoint 1)


Byte

1

2

3

4

Tx-PDO1

Obj 0x3000 (Sub 1) (status word)

0bj. 0x3003 Sub1 (Actual value 1)



NOTE

Objects 3002

hex

and 3003

hex

can be used to specify which setpoint or actual value is to be

transferred. The meaning of the setpoint or actual values is set in the frequency inverter via
parameters (P543) - (P548) for SK 500E and via parameters (P543[-01]-[-03]) or (P546[-01]
- [-03]) for SK 200E

.



Control data, profile DS301 with USS State Machine:
In order to be able to control the frequency inverter, the CANopen status must first be set to “Operational”

After switching on, the frequency inverter is in “Switch-on disabled” status. It has to be switched to "Ready for
switch-on" status using a control command. To do so, the control word “0x047E” must be transmitted. The
PDO telegram then has the following structure:

Byte

1

2

3

4

ID=204 7E

hex

04

hex

00

hex

00

hex


The drive should then run at 50% of its maximum frequency. For this purpose, the control words “0x047F” and
“0x2000” must be transmitted as setpoints:

Byte

1

2

3

4

ID=204 7F

hex

04

hex

00

hex

20

hex