Supplementary Manual CANopen for NORDAC SK 20E

62

Subject to technical amendments

BU 0260 GB

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P514

CAN baud rate (system bus)

S

0 ... 7

{ 5 }**

Setting of the transfer rate (transfer speed) via the system bus interface. All bus subscribers
must have the same baud rate setting.

0 = 10kBaud
1 = 20kBaud
2 = 50kBaud

3 = 100kBaud
4 = 125kBaud
5 = 250kBaud**

6 = 500kBaud
7 = 1Mbaud *

*) Safe operation cannot be guaranteed

**) for communication with the bus module, the parameter must be left at the factory setting
(250kBaud) otherwise no communication is possible.

P515

...

[-01]

...

[-03]

CAN address (system bus)

S

0 ... 255 dec

{ all 32 dec}

or { all 20 hex}

Setting of the system bus address.

… [-01] = Receive address for system bus

… [-02] = Broadcast – Receive address for system bus (slave)

… [-02] = Broadcast – Transmit address for system bus (master)

NOTE: If up to four SK 200E are to be linked via the system bus, the addresses must be set as follows

FI 1 = 32, FI 2 = 34, FI 3 = 36, FI 4 = 38.

The system bus addresses should be set via the DIP switches 1/2 (Section 2.2.3 ).