2 Assembly and installation

BU 0260 GB

Subject to technical amendments

27

2.2.3

Configuration

The configuration for all CANopen module versions is identical. All necessary settings are made using the
hardware via a DIP- switch element (3+8- part switching block).


Addressing
Note:

 CANopen address:

setting only via DIP switch in binary code

 Address range:

1 … 63

 Address changes:

only become effective after switching the BUS module off and on again

NOTE

If an application-specific configuration has been saved (memory object 1010

hex

), the

initialisation is not active after default mapping. In order to apply the new module ID
settings, the configuration must be reset to the factory settings (Parameter (P152) or
(Object 1011

hex

)) (See Section 4.7 “Saving the parameters”).


Termination resistor
The termination of the BUS system at both of its physical ends is carried out by connecting the relevant
termination resistors (DIP switch).

 
 
 
 
 
 
 
 
 

e.g.: SK CU4‐CAO 

e.g.: SK 200E 

CANopen module (view of DIP switch)

SK 200E (internal view)  

System bus
termination resistor

Field bus (CANopen)
termination resistor

System bus

termination resistor

Customer unit SK CU4-CAO

Technology unit SK TU4-CAO

DIP switch 3 + 8 part

BUS termination

Addressing