5 Parameterisation

BU 0260 GB

Subject to technical amendments

75

5.2.4

Module information parameters specific to the bus (P180)

Parameter

Setting value / Description / Note

Device

Supervisor

Parameter
set

P180 CANopen

address

1 ... 63

Each module transmitting on the bus must be allocated a unique address. After the new setting
of addresses, all the devices on this bus must be restarted by switching the power supply off
and on again.

Setting of addresses (node address / node ID) is only made via DIP- switches (see Section
2.2.3 "Configuration").

An address in the range between 1 and 63 must be defined. The setting "0" (all DIP switches
"OFF") is not permitted. In this case, the address 127 will be displayed in parameter (P180)

P181

CANopen baud rate

0 ... 3

Possible values:

0 = 125 kBaud
1 = 250 kBaud
2 = 500 kBaud
3 = 1 MBaud

Setting of addresses baud rate can only be made via DIP- switches (see Section 2.2.3
"Configuration").

Note:
The restriction of the cable legth for the set baud rate must be taken into account. (Section 8.1.2
"Cable material").