Supplementary Manual CANopen for NORDAC SK 20E

92

Subject to technical amendments

BU 0260 GB

Relevant

bus system

Serial

No.

Step

Comments

F

ield b

us

(CANop

en)

6

Configure bus module
for field bus

24V supply of the field bus level necessary
(see Section 2.2.3 "Configuration")

 If the bus module is the last physical subscriber in the field

bus system:

Set termination resistor:

DIP switch "Bus termination CANopen" to "ON"

 Set baud rate

 Set node address (identifier)

7

Field bus
communcation

Make bus module settings:

 (P168 [-01]):

{ 0 } "Profile OFF"

 (P162 [-01,-03,-05,-09])

{ 255 }

 (P162 [-02,-04,-06,-10])

{ 255 }

 (P163)

{ 10 }

 (P164)

{ 250 }

 (P165), (P160), (P161)

leave at factory setting

System bus

8

Monitoring at system
bus level

 (P151):

{ 200 }

 (P120 [-01])

{ 1 } or { 2 }

Field bus

(CANopen)

9

Monitoring at field bus
level (node monitoring)

 (P166 [-01]):

{ 250 }

 (P166 [-02]):

{ 400 }

 (P167):

{ 3 }

System bus

10

Checking system bus
communication

 (P748):

"System bus status"

 (P740 [-01]):

"Control word"

 (P740 [-02]):

"Setpoint 1"

 (P741 [-01]):

"Status word"

 (P741 [-02]):

"Actual value 1"

 (P173):

"Module status"

Field bus

(CANopen)

11

Checking field bus
communication

 (P173):

"Module status"

 (P176):

"PZD Bus In"

 (P177):

"PZD Bus Out"

Note: Settings specific to the application (motor data, control parameters, control terminal functions etc.)
cannot of course be described here.