NORD Drivesystems BU0260 User Manual

Page 84

Advertising
background image

Supplementary Manual CANopen for NORDAC SK 20E

84

Subject to technical amendments

BU 0260 GB

7.2.1.1 Control word (STW)

In the order telegram, in the area of the process data the control word (STW) is transferred to the frequency
inverter as the first word (taking into account the "Little Endian" format). For example, a control word "ready for
switch-on" corresponds to 047E

(hex)

, whereby in Byte 0 the value 7E

(hex)

and in Byte 1 the value 04

(hex)

are

transferred.

PZD1 PZD2 PZD3 PZD4

STW SW1 SW2/3

SW2/3

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0


Meaning of the individual bits:

Bit

Value Significance

Comments

0

0

OFF 1

Return with the brake ramp, at f=0Hz voltage activation

1 ON

Standby

1 0 OFF

2

Disable voltage; the inverter output voltage is switched off, the FI goes into
switch-on disabled status.

1 Operating

condition

OFF 2 is cancelled

2 0 OFF

3

Emergency stop with programmed emergency stop time; at f = 0Hz voltage
enable; the FI goes into switch-on disabled status

1 Operating

condition

OFF 3 is cancelled

3 0 Disable

operation Disable voltage; the inverter output voltage is switched off, the FI goes into

standby status.

1

Enable operation

Output voltage enabled, run-up to present setpoint.

4 0 Disable run-up

encoder

Run-up encoder is set to zero; at f = 0Hz no voltage enable; FI remains in
operation enabled status.

1

Operating condition

Run-up encoder is enabled

5

0

Stop run-up encoder

Freezing of actual setpoint from run-up encoder (hold frequency).

1

Enable run-up encoder Enable setpoint on run-up encoder

6

0

Disable setpoint

Selected setpoint is set to zero in the run-up encoder.

1

Enable setpoint

Selected setpoint on run-up encoder is activated.

7

0

No acknowledgement

With the switch from 0 to 1, errors which are no longer active are acknowledged.

1 Acknowledge

Note: If a digital input is programmed to the function "Error ack.", this bit must not
be set permanently to 1 via the bus (otherwise this will prevent edge detection).

8 0

1

Bit 8 active

Bus bit 8 from the control word is set. (Only for SK 200E and SK 500E)
For further details of the function please refer to parameter (P480).

9 0

1

Bit 9 active

Bus bit 9 from the control word is set. (Only for SK 200E and SK 500E)
For further details of the function please refer to parameter (P480).

10

0

PZD invalid

The transmitted process data is invalid.

1

PZD valid

Valid process data is transferred from the master.
Note:If setpoints only are transferred via the bus, this bit must be set so that the
transferred setpoint is valid.

11 0

1 Rotation

right

Rotation right (priority) is on.

12 0

1 Rotation

left

Rotation left is on.

13 0/1

Reserved

14 0/1 Parameter set switch

Bit 0

00 = Parameter set 1
01 = Parameter set 2

10 = Parameter set 3
11 = Parameter set 4

15 0/1 Parameter set switch

Bit 1