NORD Drivesystems BU0260 User Manual

Page 32

Advertising
background image

Supplementary Manual CANopen for NORDAC SK 20E

32

Subject to technical amendments

BU 0260 GB

3.1.2.2 CANopen displays

The status of the CANopen module is indicated by the CR and CE LEDs.
CR (CANopen RUN) indicates the status of the CANopen bus status machine.
CR (CANopen ERROR) indicates the status of the CANopen bus state.

Displays of the CANopen bus status machine

LED (green)

CR

CANopen RUN

Significance

...

Single flashing = (0.2s cycle)

...

Double flashing (1.6s cycle, flashing interval 0.2s)

OFF

Module not in operation

ON

OPERATIONAL

"Normal operation" → complete reference data communication

(PDO communication is "on")

Flashing

(simple)

STOPPED

Only NMT communication possible (monitoring and initialisation functions)

Flashing

(double)

PRE-OPERATIONAL

Restricted reference data communication

→ SDO communication is "on"

→ PDO mapping possible

→ PDO communication is "off"



CANopen bus status display

LED (red)

CE

CANopen ERROR

Significance

...

Single flashing = (0.2s cycle)

...

Double flashing (1.6s cycle, flashing interval 0.2s)

OFF No

error

ON

Bus OFF

Flashing

(simple)

Bus Warning

No other subscribers present

No valid ID (DIP switch = 0) (See Section 2.2.3 "Configuration")

Bus error

Wiring faulty

→ Check cable length

→ Avoid spur cables

Flashing

(double)

Timeout

A process data monitoring function has triggered

→ Node-guarding or

→ The time set in parameter (P151) has expired without

new process data being received

Note:

The "node-guarding" error is reset by restarting the monitoring (remote).