7.4.2

Example telegrams

Various example telegrams are shown below to clarify the control and parameterisation of the frequency
inverter with the various field bus systems.

7.4.2.1 Example for switching the frequency inverter on and off

In this example, a FI will be operated with a setpoint (setpoint frequency) and an actual value (actual
frequency). The "maximum frequency" is 50Hz.

Parameter settings:

 P105 = 50
 P543 = 1
 P546 = 1

Control
word

Setpoint 1

Status

word

Actual

value 1

Explanation

- - -

- - -

0000

hex

0000

hex

- - -

- - -

xx40

hex

0000

hex

The mains voltage is switched on at the FI

047E

hex

0000

hex

xx31

hex

0000

hex

FI is set to "Standby" status

047F

hex

2000

hex

xx37

hex

2000

hex

FI is set to "Operation enabled" status and controlled with a
50% setpoint.

The FI is enabled, the motor is supplied with current and rotates with a frequency of 25Hz.

0047E

hex

2000

hex

xx31

hex

0000

hex

FI is set to "Standby" staus, the motor runs up its
parameterised ramp to speed 0 and is switched off.

The FI is disabled again and the motor is without current.

047F

hex

1000

hex

xx37

hex

1000

hex

FI is set to "Operation enabled" status and controlled with a
25% setpoint.

The FI is enabled, the motor is supplied with current and rotates with a frequency of 12.5Hz.

7.4.2.2 CANopen with USS process data

The following example is designed to clarify control using PDOs. The following settings are assumed:

 FI 1 on field bus module SK xU4-CAO
 Node-ID

"4"

 Parameter (P509) "Source control word"

for SK500E: Setting: {6} "CANopen control word" (object number (21FD

hex

) = 6) or

for SK200E: Setting: {3} "System bus" (object number (21FD

hex

) = 3,

(P510)= {0}

 Rx-PDO1 is used for control. The device transmits its actual values via Tx-PDO1
 The drive profile is disabled

for SK 500E: Setting: (P551) = {0} or
for SK200E: Setting: (P168 [-01]) = {0}

Identifier

Rx-PDO1: 0200

hex

+ NODE-ID

 0204

hex

Tx-PDO1: 0180

hex

+ NODE-ID

 0184

hex