7 CANopen Data transfer

BU 0260 GB

Subject to technical amendments

95

7.4.2.3 Application-specific mapping

Instead of using the default mapping, an application-specific mapping can define which data is to be
transmitted by means of PDOs. For this, the module must be in "Pre-Operational" status or should be put in
this status with the NMT service "Enter Pre-Operational".
The procedure for an application-specific mapping is explained on the basis of a specific example.

Example:
With the aid of a Transmit PDO, the control word and setpoint 3 are to be transferred to the frequency inverter
with a data width of 16 bit.

The CAN identifier 0x432 is to be used for the transfer.

The transfer is to be carried out sychronously with each third SYNC object.

The default CAN-IDs are used for the SDOs.



Changes to the mapping for the Transmit PDO1

Deactivation of Transmit PDO 1

Deactivation of the PDO mapping by setting "0" - Setting of the number of mapping objects in Index 0x1A00,
Sub-Index 0 (Transmit PDO Mapping Parameter).

CAN-ID

Data

Transmit

0x0600

0x2F 00 1A 00 00 xx xx xx

Receive

0x0580

0x60 00 1A 00 xx xx xx xx


Entering the mapping objects
Entry in the Transmit PDO mapping structure (Index 0x1A00) of:

 Index
 Sub-index

Object length of the application object

A maximum of 8 bytes of data can be assigned to each PDO.

Application object

Index

Sub-index

FI 1 control word

0x3000

1

FI 1 Setpoint 3

0x3002

3


The following structure must be achieved in the mapping parameters of the 1st Transmit PDO (Objekt 0x1A00).

Sub-index

Index

Sub-index

Object length in bits

Comments

0 2

Number of mappings

1 0x3000

1

0x10

FI 1 control word

2 0x3002

3

0x10

FI 1 Setpoint 3

NOTE

The number of valid sub-indices are only entered into Sub-Index 0 after the mapping
parameters in Sub-Index 1 ... 8 have been entered.