Supplementary Manual CANopen for NORDAC SK 20E

90

Subject to technical amendments

BU 0260 GB

Relevant

bus system

Serial

No.

Step

Comments

System bus

1

Set up system bus

24V supply of the system bus level necessary

(see Section 2.2.2.2 "Control connections

of the SK

CU4-CAO(-...)

")

2

Set termination resistor

 DIP switch "Bus termination, system bus" on CAO module "ON"

 DIP switch "Bus termination, system bus" on FI 3 "ON"

 All other DIP switches to "OFF"

3

Set system bus
addresses

Setting of FI addresses preferably via DIP switches (see manual
BU0200):

 Bus module:

fixed (at 5)

 FI 1:

to 32

 FI 2:

to 34

 FI 3:

to 36

4

System bus baud rate

set to 250kBaud for FI and bus module
(is preset accordingly)

5

System bus
communication

Make settings on each FI

 (P509):

{ 3 } "System bus"

 (P510 [-01 … -02]):

{ 0 } "Auto"

 (P543 [-01]):

{ 1 } "Actual frequency"

 (P546 [-01]):

{ 1 } "setpoint frequency"

F

ield b

us

(CANop

en)

6

Configure bus module
for field bus

24V supply of the field bus level necessary
(see Section 2.2.3 "Configuration")

 If the bus module is the last physical subscriber in the field

bus system:

Set termination resistor:

DIP switch "Bus termination CANopen" to "ON"

 Set baud rate

 Set node address (identifier)

7

Field bus
communcation

Make bus module settings:

 (P168 [-01]):

{ 1 } "Profile ON"

 (P168 [-02]):

{ 3000 } „+∆n (FI 1)"

 (P168 [-03]):

{ 6 } „+ ∆t (FI 1)"

 (P168 [-04]):

{ 3000 } „- ∆n (FI 1)"

 (P168 [-05]):

{ 6 } „- ∆t (FI 1)"

 (P168 [-06]):

{ 1500 } „+∆n (FI 2)"

 (P168 [-07]):

{ 4 } „+ ∆t (FI 1)"

 …

 (P162 [-01,-03,-05,-09])

{ 255 }

 (P162 [-02,-04,-06,-10])

{ 255 }

 (P163)

{ 10 }

 (P164)

{ 250 }

 (P165), (P160), (P161)

leave at factory setting

System bus

8

Monitoring at system
bus level

 (P151):

{ 200 }

 (P120 [-01])

{ 1 } or { 2 }

Field bus

(CANopen)

9

Monitoring at field bus
level (node monitoring)

 (P166 [-01]):

{ 250 }

 (P166 [-02]):

{ 400 }

 (P167):

{ 3 }

System bus

10

Checking system bus
communication

 (P748):

"System bus status"

 (P740 [-01]):

"Control word"

 (P740 [-02]):

"Setpoint 1"

 (P741 [-01]):

"Status word"

 (P741 [-02]):

"Actual value 1"

 (P173):

"Module status"

Field bus

(CANopen)

11

Checking field bus
communication

 (P173):

"Module status"

 (P176):

"PZD Bus In"

 (P177):

"PZD Bus Out"


Note: Settings specific to the application (motor data, control parameters, control terminal functions etc.)