6.2 Error messages

6.2.1

Table of possible error messages (caused by the bus) in the frequency inverter

The following error messages concern bus-related messages which are indicated on the frequency inverter.
A complete list of error messages for the frequency inverter (SK 200E) can be found in the relevant manual
(BU0200).

Error code
display on the
SimpleBox

Fault

Text in the ParameterBox

Cause

Remedy

Group

Details in
P700 / P701

E010

10.2

External bus module
telegram timeout

Telegram transfer is faulty.

Check external connection.

Check bus protocol program process.

Check bus master.

10.3

Timeout via (P151)

Telegram transfer is faulty.

Check watchdog time (P151)

Check physical bus connections

Contains cyclic telegrams

10.4

External bus module
initialisation failure

Bus module cannot be accessed

Check bus module power supply

10.8 External

module

communication failure

Connection fault / error in the external module to the FI

10.9

Module not found

The module entered in parameter (P120) is not available.