7 CANopen Data transfer

BU 0260 GB

Subject to technical amendments

83

ATTENTION

If parameter changes are made, care must be taken that the maximum number of
permissible writing cycles to the frequency inverter EEPROM (100,000 cycles) is not
exceeded. I.e. continuous cyclical writing must be prevented.
For certain applications it is sufficient if the values are only saved in the RAM memory of the
frequency inverter. The corresponding setting is made via parameter (P560) "Save in
EEPROM".
Note: This does not apply to parameters which relate to the bus module ((P150) to (P199)).
Here too, the EEPROM only permits a maximum of 100,000 writing cycles. However, the
parameters are only written into the EEPROM if access is made via the ParameterBox or
NORDCON, or if the parameter values are changed in the bus module by means of SDOs.


7.2.1

Process data (PZD) in USS standard

In the process data area PZD, control words and setpoints or status words and actual values are transferred
from one node (frequency inverter) to another. The structure of the PZD area is always the same with regard to
the sequence of its elements (words (= 2 bytes each)) whereby the processing of the individual bytes is carried
out by the typical CAN method according to the "Little Endian" format.

The process data area of the reference data has the following structure:

- STW:

Control Word; length 16 bit, order telegram contains control bits (e.g. enable, rapid stop, error

acknowledgement)

- ZSW: Status Word; length 16 bit, response telegram contains status bits (e.g. FI running, fault)

- SW1..3: Setpoints; maximum 3 possible, 16 or 32 bit, order telegram

e.g. frequency setpoint, position setpoint, torque setpoint

- IW1..3: Actual Values; maximum 3 possible, 16 or 32 bit, response telegram

e.g. actual frequency value, actual position value, actual torque value



1. Word

(Byte 0,1)

2. Word

(Byte 2,3)

3. Word

(Byte 4,5)

4. Word

(Byte 6,7)

PZD area with

1x16 bit setpoint

STW
ZSW

SW1

IW1

PZD area with up to 3

16 bit setpoints

STW
ZSW

SW1

IW1

SW2

IW2

SW3

IW3

Note: 32 bit setpoints (e.g.: positions) are comprised of High or Low words (each 16 bit), whereby

according to the Little Endian format, processing starts with the Low word.